How the BTU calculator works
The calculator estimates a room's cooling or heating capacity, or converts an existing capacity between units. Cooling starts with ENERGY STAR's room air conditioner chart. Heating uses a simplified volume-and-temperature model with assumed insulation factors.
A BTU is energy; BTU/h is a rate of heat transfer. Air conditioner and heater capacities belong in BTU/h, even when a product description shortens the label to BTU. Cooling capacity describes heat removed, while heating capacity describes heat supplied.
- 1Choose cooling, heating or convert. Cooling estimates room air conditioner capacity. Heating estimates heat demand under your chosen conditions. Convert accepts a capacity in BTU/h, refrigeration tons, watts or kilowatts.
- 2Enter the room measurements. For cooling or heating, enter length and width, or a known floor area, then ceiling height. Use feet or meters and square feet or square meters. For an irregular floor plan, calculate the combined area of its smaller sections.
- 3Set the room conditions. Cooling needs sun exposure, regular occupant count and whether the room is a kitchen. Heating needs indoor and outdoor temperatures and an insulation preset. Results show BTU/h and equivalent capacity units, with the working and a chart or preset comparison.
Cooling capacity from room area
ENERGY STAR's chart gives a starting capacity for rooms with an 8 ft ceiling. The calculator looks up the floor area without interpolating between rows. At a shared boundary, it uses the row beginning at that area; the final row includes 2,500 ft².
| Floor area (ft²) | Capacity (BTU/h) |
|---|---|
| 100 to <150 | 5,000 |
| 150 to <250 | 6,000 |
| 250 to <300 | 7,000 |
| 300 to <350 | 8,000 |
| 350 to <400 | 9,000 |
| 400 to <450 | 10,000 |
| 450 to <550 | 12,000 |
| 550 to <700 | 14,000 |
| 700 to <1,000 | 18,000 |
| 1,000 to <1,200 | 21,000 |
| 1,200 to <1,400 | 23,000 |
| 1,400 to <1,500 | 24,000 |
| 1,500 to <2,000 | 30,000 |
| 2,000 to 2,500 | 34,000 |
Apply height and sun factors to the chart capacity first. Add the occupant and kitchen allowances afterward. All capacity terms are in BTU/h.
The sun, occupant and kitchen adjustments follow ENERGY STAR: subtract 10% for heavy shade, add 10% for strong sun, add 600 BTU/h per person beyond two, and add 4,000 BTU/h for a kitchen. Fewer than two occupants do not reduce capacity.
The height multiplier is a separate calculator assumption, not an ENERGY STAR formula. It increases the base capacity in proportion to height above 8 ft, with no reduction for lower ceilings. It cannot account for the actual heat gains of a vaulted room.
Worked cooling example
The default cooling example is a 500 ft² room with a 9 ft ceiling, strong sun and four regular occupants. Kitchen is off. Its base capacity is 12,000 BTU/h.
- Height adjustment: 12,000 × 9 ÷ 8 = 13,500 BTU/h.
- Sun adjustment: 13,500 × 10% = 1,350 BTU/h.
- Additional occupants: (4 − 2) × 600 = 1,200 BTU/h.
- Total: 13,500 + 1,350 + 1,200 = 16,050 BTU/h.
Heating capacity from volume and temperature
Heating mode multiplies room volume by the indoor-to-outdoor temperature difference and an assumed volumetric heat-loss factor. It estimates the heat needed to maintain a temperature under those assumptions, not how long the room takes to warm up.
For the factors below, use volume in ft³ and temperatures in °F. Room volume equals floor area × ceiling height.
These insulation presets are illustrative calculator assumptions, not standardized insulation ratings or measured building properties. Actual heat loss depends on exposed surface areas, their U-values and air leakage. An insulation label alone does not establish those values.
| Insulation preset | Assumed factor k | Heating estimate (BTU/h) |
|---|---|---|
| Excellent | 0.093 | 11,160 |
| Good | 0.113 | 13,560 |
| ModerateExample | 0.133 | 15,960 |
| Poor | 0.153 | 18,360 |
| Very poor | 0.173 | 20,760 |
The default heating example is 15 × 20 ft with an 8 ft ceiling, Moderate insulation, 70 °F indoors and 20 °F outdoors. Volume is 2,400 ft³ and the temperature difference is 50 °F. The calculation is 2,400 × 50 × 0.133 = 15,960 BTU/h, equivalent to 4.68 kW of heat.
Metric entries must give the same result after conversion. The equivalent metric factor is k × 18.6295 in W/(m³·°C); Moderate becomes about 2.478. Use the temperature difference, not an absolute-temperature conversion. If indoors is no warmer than outdoors, this heating model returns zero.
Convert BTU/h to tons, watts and kilowatts
Conversions use the International Table BTU. One refrigeration ton equals 12,000 BTU/h. Enter a nonnegative capacity and its unit; the other values describe the same heat-transfer rate.
Watts and kilowatts here describe thermal capacity, not necessarily electrical input.
| BTU/h | Refrigeration tons | Thermal kW |
|---|---|---|
| 6,000 | 0.50 | 1.76 |
| 12,000 | 1.00 | 3.52 |
| 18,000 | 1.50 | 5.28 |
| 24,000 | 2.00 | 7.03 |
| 36,000 | 3.00 | 10.55 |
Check the estimate before choosing equipment
- 1Stay within the cooling chart's scope. The chart covers 100–2,500 ft². Do not extend its top row as a fixed capacity-per-square-foot rule for larger spaces.
- 2Use a winter design temperature. For heating, use the local outdoor design temperature appropriate to equipment sizing, not an annual average or an arbitrary record low.
- 3Compare delivered capacity. The heating estimate is useful heat required by the room, not a furnace's fuel-input rating. Equipment selection also needs operating conditions and distribution losses.
Frequently asked questions
What size air conditioner does a 12 × 12 ft room need?
Its 144 ft² floor area starts at 5,000 BTU/h. With an 8 ft ceiling, average sun, no more than two regular occupants and no kitchen allowance, that remains the result. Very sunny conditions increase it to 5,500 BTU/h.
How many BTUs per hour are in a ton?
One refrigeration ton is 12,000 BTU/h. A 2-ton cooling capacity is therefore 24,000 BTU/h.
How many BTUs per hour is a 1,500 W heater?
A thermal output of 1,500 W equals about 5,118 BTU/h. This conversion describes heat output; it does not by itself establish how much electricity a heating system uses.
Should I always buy the next larger air conditioner?
No. ENERGY STAR warns that an oversized room air conditioner can cool the room before removing enough humidity. The calculated estimate is not an automatic instruction to round up to the next product size.
Can I use this result to size a mini-split or a whole-house system?
Treat it as an initial comparison only. The room AC chart and illustrative heating presets do not replace a residential load calculation. ACCA Manual J accounts for building and climate details needed before equipment selection.
Sources
- 1Room Air Conditioners · ENERGY STAR · Accessed November 2026
- 2ENERGY STAR Sales Associate Training: Room Air Conditioners · U.S. Environmental Protection Agency · Accessed November 2026
- 3NIST Guide to the SI, Appendix B.9: Factors for units listed by kind of quantity or field of science · National Institute of Standards and Technology · Accessed November 2026
- 4Energy in buildings: Calculating the total heat loss of a house · The Open University · Accessed November 2026
- 5HVAC Proper Sizing of HVAC Systems · U.S. Department of Energy · Accessed November 2026
Sizing results are estimates; have an HVAC professional calculate the load before selecting permanent heating or cooling equipment.